IEEE Std C37.91-2021 

Protecting Power Transformers

6.5 Reasons of Mismatch

6. Relay Currents

6.5 Reasons of Mismatch

Non-fault related currents or factors can indeed influence the operation of differential relays. These can cause a differential current to flow even in the absence of a fault. It is necessary to understand these factors and implement compensatory measures to ensure accurate and reliable relay operation. 

6.5.2 Unbalance caused by CT ratios 

It can be challenging to match Current Transformer (CT) ratios exactly on both sides of a transformer, even when the transformer has a fixed ratio. This mismatch results in differential currents flowing in the operating circuits of differential relays, potentially causing undesired relay operations.

The OLTC dynamically adjusts the transformer's turn ratio to maintain a constant secondary voltage despite variations in the primary voltage or load. However, this introduces an additional layer of complexity as the CT ratios should be matched according to the OLTC position.

The DETC is usually adjusted when the transformer is offline to adapt to changes in the overall system condition or load pattern. If the relay settings are not updated accordingly, it can cause a large discrepancy between the actual and expected CT ratios.

The differential operating current due to mismatch can be significantly large. This could potentially lead to false tripping of the differential relay.

6.5.3 Magnetizing inrush 

Phenomenon:

Magnetizing inrush is a phenomenon that contradicts the fundamental principle of differential relaying. This occurs when the primary winding of a transformer is connected to a source and the secondary winding is connected to loads. In such a situation, magnetizing inrush currents flow from the source to the primary winding while little or no current flows from the transformer's secondary windings.

Situations:

Severe magnetizing inrush phenomena:

Energizing of a transformer at a station where at least one other transformer is already energized. This inrush event affects both the already-energized transformers and the transformer being energized, and the transient inrush could potentially last for an extended duration.

Interestingly, the inrush into the transformer being energized happens during the opposite half-cycle to that of the already energized transformer. Consequently, the total inrush into all transformers might resemble into a sine wave of the base frequency. This means that the harmonic restraint element of a differential relay, which might be protecting both parallel-connected transformers, would not be activated.

While the inrush is not more severe in this situation than in a regular inrush, the issue is that there is inrush current flowing from the previously energized transformer to the incoming transformer. The combined inrush to both transformers has minimal second harmonic. As a result, it's preferable to equip each parallel-connected transformer with its own differential relay for optimal protection.

Harmonic content

The harmonic content of the inrush current is influenced by several factors, including 


Analysis reveals that the second-harmonic content of the inrush current is particularly sensitive to these conditions. As the load at a lagging power factor increases, the second-harmonic content noticeably decreases.

Reduction in magnetizing inrush

A significant reduction in magnetizing inrush currents can be achieved by using three single-phase point-on-wave closing circuit breakers to switch a transformer. 

6.5.4 Magnetizing current during overexcitation 

Power Plant Phenomena:

Several phenomena can cause overexcitation in a transformer, sometimes in conjunction with significant overvoltage at the nominal frequency. Some of these occurrences can happen which may involve an overvoltage significantly above nominal:

Transmission Phenomena:

In the transmission system, overexcitation at nominal frequency with potentially substantial overvoltage can result from various control failures such as 

If transformer saturation happens, substantial exciting current flows can overheat the transformer's core, tank, or structure, causing damage. The waveform in such instances is distorted, containing harmonic content and near zero-current periods. 

Overexcitation distorts the waveform, but the positive and negative half-cycle behavior remains the same, leading to only odd harmonics and no noticeable even harmonics that appear during inrush. Hence, the presence of third and fifth harmonics indicates overexcitation. The extent of these effects depends on the generator connections and the transformer design and connections.


Typical Transformers Overexcitation Scenarios: